Home/Engineering & CS/Available SC: 500 MVA X/R: 6 1. Calculate the symmetrical 3ph fault current at point F1 1MVA, 13.8kV/480V Z = 5.75% 3 - 175mm2 (350kcmil) Cu in steel conduit, 30.5m F1 open line Each feeder supplies mixed lighting and motors with total combined motor of 250hp
Question
Solved1 AnswerAvailable SC: 500 MVA X/R: 6 1. Calculate the symmetrical 3ph fault current at point F1 1MVA, 13.8kV/480V Z = 5.75% 3 - 175mm2 (350kcmil) Cu in steel conduit, 30.5m F1 open line Each feeder supplies mixed lighting and motors with total combined motor of 250hp
LAYMK4The Asker · Electrical Engineering
Transcribed Image Text: Available SC: 500 MVA X/R: 6 1. Calculate the symmetrical 3ph fault current at point F1 1MVA, 13.8kV/480V Z = 5.75% 3 - 175mm2 (350kcmil) Cu in steel conduit, 30.5m F1 open line Each feeder supplies mixed lighting and motors with total combined motor of 250hp
More
Transcribed Image Text: Available SC: 500 MVA X/R: 6 1. Calculate the symmetrical 3ph fault current at point F1 1MVA, 13.8kV/480V Z = 5.75% 3 - 175mm2 (350kcmil) Cu in steel conduit, 30.5m F1 open line Each feeder supplies mixed lighting and motors with total combined motor of 250hp
See Answer
Add Answer +20 Points
Community Answer
4JEP6PThe First Answerer
See all the answers with 1 Unlock Get 4 Free Unlocks by registration
false
Given z=5.75%for a three phase fault.{:[I_(f)=(1)/(2)=(1)/(5.75 xx100)=17.39pu] ... See the full answer